7. Locate the 3-circuit connector in the control/end bell. Using an ohmmeter, check the resistance
8. Reassemble motor and control/end bell in reverse of disassembly. Replace blower assembly
Motor Checks
Warning
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
1. Disconnect power to air handler or modular blower.
2. Disassemble motor as described in steps 2 through 4 above.
3. Locate the 3-circuit harness from the motor. Using an ohmmeter, measure the resistance
4. Measure the resistance between each motor phase winding and the motor shell. Replace the
5. Reassemble motor and control/end bell in reverse of disassembly. Replace blower assembly
Part 6 Service Diagnosis
between each terminal in the connector. If the resistance is 100  or greater, the control/end
bell is functioning properly. Replace the control/end bell if the resistance is lower than 100 .
into air handler or modular blower.
NOTE: Motor contains capacitors that can hold a charge for several minutes after disconnecting
power. Wait 5 minutes after removing power to allow capacitors to discharge.
between each motor phase winding. The resistance levels should be equal. Replace the motor
if the resistance levels are unequal, open circuited or short circuited.
motor if any phase winding is short circuited to the motor shell.
into air handler or modular blower.