Daikin SkyAir RZR-TA Series Service Manual page 97

Cooling only 60 hz heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811E
According to the current limit of direct current
Existing DC power limit
requirement.
Limited
10 seconds
Matching
OR
frequency
15 seconds
No DC power limit
requirement continuously
for 3 minutes.
Part 4 Functions and Control
Not limited
Compressor stopped
OR
Inverter upper limit frequency:
1-step down from current
compressor frequency
Current step maintained
Inverter upper limit frequency:
1-step up from current
compressor frequency
No DC power limit requirement.
Compressor upper limit : Maximum frequency
Existing DC power
limit requirement.
Without conditions
Protection Control
91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents