Troubleshooting by Error Codes
4.7

Drain Level Control System (S1L) Abnormality

A3
Error Code
Applicable
FCQ-TA, FBQ-P
Models
Method of Error
By float switch OFF detection
Detection
Error Decision
When the float switch goes OFF when conditions for rise of water level are not met
Conditions
Supposed
 Defective drain pump
Causes
 Improper drain piping work
 Drain piping clogging
 Defective float switch
 Defective indoor unit PCB
 Defective short circuit connector on PCB