SiUS281811E
Troubleshooting
Note(s)
1: Make a comparison between the voltage of the pressure sensor and that read by the
Reference
CHECK 1 Refer to page 261.
Reference
CHECK 12 Refer to page 273.
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check for the points shown below.
(1) Is the stop valve open?
(2) Is the high pressure switch connector properly
connected to the main PCB?
(3) Does the high pressure switch have continuity?
Are the three points
above OK?
YES
(1) Mount a pressure gauge on the high pressure
service port.
(2) Reset the operation using the remote controller,
and then restart the operation.
YES
Does the abnormal
stop E3 recur?
NO
Are the
characteristics of the
high pressure sensor
normal? ( 1)
YES
Service Checker
CHECK 12
Compare the high pressure value checked with the Service Checker and
the actual value measured by pressure sensor ( 1).
Check
if the high
pressure value and the
actual value measured by
pressure sensor are
the same.
YES
· The high pressure sensor is normal, and the pressure detected with the PCB is also normal.
· The high pressure has really become high.
CHECK 1 Remove the causes by which the high pressure has become high.
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the
connector, and then convert it to pressure. CHECK 12)
NO
Is the
high pressure
NO
switch operating value
normal (4.0 MPa
(580 psi))?
YES
NO
NO
Troubleshooting by Error Codes
Rectify the defective points,
if any.
Replace the high pressure switch.
Replace the high pressure sensor.
Replace the outdoor main
PCB (A1P).
223