Drain Pump Control - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811E
6.7

Drain Pump Control

6.7.1 Normal Operation
 The float switch is ON in normal operation.
 When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
 After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
 The aim of residual operation after thermostat OFF is to eliminate the dew that condenses on
6.7.2 If the Float Switch is OFF with the Thermostat ON in Cooling Operation
 When the float switch turns OFF, the thermostat turns OFF simultaneously.
 After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
1. If the float switch turns ON again during the residual operation of the drain pump, cooling
2. If the float switch remains OFF even after the residual operation of the drain pump has
3. The drain pump turns OFF once residual operation has ended, then turns ON again after
4. After A3 is displayed and the unit comes to an abnormal stop, the thermostat will remain
Part 4 Functions and Control
OFF
Float switch
ON
ON
Thermostat
(running)
OFF
ON
Error display
OFF
ON
Drain pump
OFF
the indoor heat exchanger during cooling operation.
OFF
Float switch
ON
ON
Thermostat
(running)
OFF
ON
Error display
OFF
ON
Drain pump
OFF
operation also turns on again (thermostat ON).
ended, the error code A3 is displayed on the remote controller.
5 seconds.
OFF even if the float switch turns ON again.
5 min.
2
1
3
5 min. 5 sec.
5 min.
5 sec.
Outline of Control (Indoor Unit)
4
A3
101