Franklin Fueling Systems EVO 200 Programming Manual page 46

Automatic tank gauges
Hide thumbs Also See for EVO 200:
Table of Contents

Advertisement

FMS alarms (continued)
Displayed
Alarm/Warning
Manifold Leak
Detected
Manifold low product
volume
Manifold low low
product volume
Manifold Leak
Detected
Manifold Theft
Detected
Monthly Compliance
Alarm
Monthly Compliance
Warning
Net error
No data available
No probe detected
Probe
synchronization error
Product volume error
RTD table error
System memory error
40
Device
Description
Tank
A leak in the specified manifolded
tanks has been detected via a
SCALD® test. Suspect possible leak
Tank
The specified manifold has reached
the programmed Low Product
Volume
Tank
The specified manifold has reached
the programmed Low Low Product
Volume
Tank
A leak in the specified manifolded
tanks has been detected via a
SCALD® test. Suspect possible leak.
Tank
The specified manifold has entered
Sentinel Mode and detects product
leaving the tank that exceeds the
programmed theft limits.
Any
The device listed has gone out of
compliance
Any
The device listed has 7 days before it
will go into a compliance alarm.
Tank
Product net levels exceed tank
diameter
System
A communication issue has occurred
between the probe and the console
Tank
The Console is not receiving any
communication from the probe.
Tank
Communication between the probe
and the Console is either incomplete
or ill timed.
Tank
The Product Volume as reported by
the probe has exceeded the limits of
the tank.
Tank
RTD distance error; Special Probe
programming error.
System
The system has detected a low
memory situation.
Recommended Actions
Review Tank Leak Test History and programming.
Refer to Tank Testing in the Operation Guide.
Check product volume and compare to the
programmed Low Volume alarm Limit in the
setup menu. Acquire an accurate product volume
and compare to the ATG. If levels differ, verify
programming is correct. If alarm persists, contact
FFS Technical Services for support.
Check product volume and compare to the
programmed Low Low Volume alarm Limit in the
setup menu. Acquire an accurate product volume
and compare to the ATG. If levels differ, verify
programming is correct. If alarm persists, contact
FFS Technical Services for support.
Review Tank Leak Test History and programming.
Refer to Tank Testing in the Operation Guide.
Verify programming and accurate level / volume
readings.
Pass a test or clear the alarm on the device.
Pass a test or clear the alarm on the device.
Verify tank, product offset and probe programming
Check for proper probe programming at the console
and inspect wire connections at the probe. If the
problem persists, contact FFS Technical Services for
support.
Check for proper probe programming at the console
and inspect wire connections at the probe. If the
problem persists, contact FFS Technical Services for
support.
Check for proper probe programming at the console
and inspect wire connections at the probe. If the
problem persists, contact FFS Technical Services for
support.
Check for proper probe and tank programming at
the console. If programming is correct, inspect the
probe to ensure that the float is not stuck in the
riser or is otherwise obstructed.
Verify correct RTD programming. If issue still exists,
inspect wiring to probe.If the condition still exists,
contact Franklin Fueling Systems' Technical Services
for support.
Contact FFS Technical Services for support.