Information On Grounded Pv Plants; Reverse Voltage; Personnel; General Information - SMA SUNNY STRING-MONITOR Technical Description

Accessories for central inverter
Table of Contents

Advertisement

SMA Solar Technology AG
2.3.2 Information on Grounded PV Plants
The positive or negative pole of the PV array can be grounded within the Sunny Central via a GFDI
(Ground Fault Detection Interruption) fuse.
• Additional grounding within the PV array or floor-mounted distribution board is not permissible.
The grounding of the PV array can be automatically interrupted by the GFDI at any time.
• The GFDI ensures plant protection, but does not protect persons.
You will find additional information on grounded PV plants in the Sunny Central documentation and
in the download area of www.SMA.de/en.
2.3.3 Reverse Voltage
On the main DC cables in the Sunny String-Monitor there is a permanent reverse voltage present of
up to 1000 V
of the Sunny Central. When the power is off, the reverse voltage can be interrupted
DC
by pulling the DC fuses in the Sunny Central.
2.4 Personnel
Only qualified technical personnel may perform work on the Sunny String-Monitor. Qualified means
that the personnel must possess training relevant to the activity performed and must be familiar with
the content of this manual.
2.5 General Information
Communication between Sunny String-Monitor and Sunny Central
Alongside the Sunny String-Monitor SSM one can also install the Sunny String-Monitor SSM16-11 as
well as the Sunny String-Monitor SSM24-11 for string monitoring These have various numbers of
Piggy-Backs for data processing.
Maximum number of Piggy-Backs for data processing
There are two communications connections in each Sunny Central, to which up to 10
Piggy-Backs each can be connected. The number of Piggy-Backs for data processing is
thus determined by the combination possibilities between the Sunny String-Monitor SSM,
Sunny String-Monitor SSM16-11 and Sunny String-Monitor SSM24-11. The following
summary shows the number of Piggy-Backs for data processing in the various Sunny
String-Monitor:
• Sunny String-Monitor SSM: 1 Piggy-Back for data processing.
• Sunny String-Monitor SSM16-11: 2 Piggy-Backs for data processing.
• Sunny String-Monitor SSM24-11: 3 Piggy-Backs for data processing.
Technical Description
2 Safety
SSM-TEN103132
13