Hellenbrand H-200M Series Owner's Manual page 15

Water conditioning system
Table of Contents

Advertisement

SYSTEM BOARD
STEP 10CS
ENABLED
SET
HP Manual
AUX MAV OFF
STEP 11CS
TRIGGER
STEP 5CS
SET
Brine Reclaim: When Reclaim is selected as trigger for Auxilliary MAV Drive, a portion of the brine can be diverted after it has passed through
the resin bed. Brine discharge contains unused salt that can be used for brine make-up for the next regeneration. A motorized alternator valve
(MAV) must be connected to the two-pin connector labeled AUX DRIVE located on the circuit board or error code 106 will result. The MAV
diverts the brine discharge to brine tank. A-Port discharges to brine tank. B-Port discharges to drain, remaining port connects to the valve drain
fitting. Elution study should be done to provide settings that optimize salt savings without sacrificing capacity. Three reclaim events are pos-
sible, use up arrow to select reclaim enabled for one reclaim event, reclaim 2x for two reclaim events and reclaim 3x for three events.
RECLAIM START
30:00
STEP12CS
MIN
SET
RECLAIM DURATION
STEP 13CS
6:00
MIN
SET
AUX MAV SEP SOURCE
STEP 14CS
TRIGGER
SET
15
STEP 10CS – Configuring the Control Valve to operate with the Hellenbrand SystemMate
Controller - Select System Board Enabled to link the Control Valve to the SystemMate Controller. For
communication between the Control Valve and the System Controller, a three wire communication cable
is required.
Press NEXT to go to Step 11CS. Press REGEN to return to previous step.
STEP 11CS – Use the  or  buttons to select one of the following:
• Reclaim – Allows brine reclaimation – Press NEXT to go to Step 12CS.
• Separate Source –Allows Auxiliary MAV to switch positions before the start of regeneration and to
Step 5CS – Set Auxiliary Drive Output (MAV only) to operate in one of three modes:
switch back at the end of regeneration. See instructions in Step 14CS.
• Set RECLAIM (Time): Allows Auxiliary MAV to switch positions at a set time in relation to the start
• Off - Factory Setting is Off
of regeneration for a preset duration, independently of the actual regeneration status. Up to 3 bypass
Press NEXT to go to Step 12CS when reclaim selected as trigger. Press REGEN to return to previous
events are possible.
step.
• Set SEP SOURCE: Allows Auxiliary MAV to switch positions before the start of regeneration and
then switch back at the end of regeneration.
• Set OFF: Deactivates this output.
Only use Clack Motorized Alternating Valves (MAV) with these selections. Clack No Hard Water Bypass
Valves (1" or 1.25" V3070FF or V3070FM) are not designed to be used with the reclaim or separate source
functions.
Press NEXT to go to Step 6CS. Press REGEN to return to previous step.
STEP 12CS – Only displays if reclamation of brine is enabled in Step 11CS. Use the  or  buttons to
select the number of minutes after the start of regeneration before the MAV will divert the brine waste wa-
ter from the plumbing drain receptacle to the brine tank. Start of regeneration is defined as any mode that
is not fill or softening. MAV automatically returns to service when manually stepping through regeneration.
Elution study is recommended to optimize salt savings without sacraficing capacity.
Press NEXT to go to Step 13CS. Press REGEN to return to previous step.
STEP 13CS – Only displays if reclamation of brine is enabled in Step 11CS. Use the  or  buttons to
select the number of minutes to divert the brine waste water to the brine tank. After the minutes count
down to zero, the waste water will once again be diverted to the plumbing drain receptacle.
Press NEXT to go to Step 15CS. Press REGEN to return to previous step.
STEP 14CS – Separate source selection requires connection of motorized alternator valve (MAV) to
Auxiliary Drive two-pin connection on board.
Auxiliary MAV Drive set to operate with a Separate Source trigger. Auxiliary MAV transitions to Bypass
before the start of regen cycle #1, AFTER Alternator MAV motor transition. Auxiliary MAV transitions
back to Service at the completion of the last programmed regen cycle, once the Valve Motor deactivates
and BEFORE Alternator MAV transition (if scheduled). Auxiliary MAV will NOT automatically return to
Service while manually stepping valve through regen, MAV will remain in Bypass until regen cycle ends
or NEXT & REGEN buttons pushed simultaneously until display changes. Press NEXT to go to Step
15CS. Press REGEN to return to previous step.
Page 11