Programming Options; Operating Instructions For Access Level 3 Functions - Honeywell 13270-01LB Data, Installation And Commissioning Manual

Fire control and repeat panels, conventional 1, 2, 4 and 8 zone panel range
Hide thumbs Also See for 13270-01LB:
Table of Contents

Advertisement

Fire Panels

Programming Options

NOTE: There is a 2 minute
timeout on the access levels. If
this period is exceeded the
code will have to be re-entered.
In order to access the EEPROM,
the EEPROM protection link
needs removing, see Figure 14.
The default settings of the panel
may be changed to suit site
requirements..

Operating instructions for Access level 3 functions

To allow Cancel buzzer at access level 1 (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 000 000
To allow Cancel buzzer at access level 2
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 000 001
To allow Display test at access level 1
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 001 001
To allow Display test at access level 2 (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 001 002
To allow Test condition at access level 2 (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 002 002
To allow Test condition at access level 3
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 002 003
To allow most recent alarm indication as a steady state indication (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 003 000
To allow most recent alarm as a pulsing indication
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 003 001
To allow Auxiliary output to activate in fire and deactivate on reset (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 005 000
To allow Auxiliary output to activate in fire and deactivate on reset and silence alarms
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 005 001
To change the Delay mode setting (default setting is 1 minute)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 006 and data 000 to 010 in
minutes. Note if a value of greater than 10 minutes is entered, it will be truncated to 10 minutes.
4188-424 issue 4_Part 1_10-09
Factory set codes:
AL3 code is: 321
This is the code on first power-up
and it can be changed at any time.
AL4 code is: 7426
This code is for the use by the
servicing organisation only.
reset code, 2623
There is a
which will reset the AL2 and AL3
codes to their factory settings.
Whilst the EEPROM is
unprotected during programming,
the system fault light will flash to
14
Programming Options
indicate that the EEPROM
protection link is removed. If
further changes are required, the
sequence shift followed by 9000
must be re-entered.
Once the changes have been
made, the panel must be powered
down and then powered up again
for the changes to take place.
NOTE: After programming is
complete the EEPROM
protection link must be refitted.