Danger to life if the maximum permissible cable length between the Safe Brake Adapter
and the Control Interface Module is exceeded
If the permissible cable length between the Safe Brake Adapter and the Control Interface
Module is exceeded this can result in death or serious injury in the event of an error.
• The maximum permissible cable length of 10 m between the 230 VAC Safe Brake
• The cable must be routed according to ISO 13849-2, Table D.4.
• It is recommended that the cable harness (length 4 m) with article number
Table 5- 26
Terminal strip X12, 230 VAC power supply
Connection
Signal
X12.1
L
X12.2
N
Max. connectable cross-section 2.5 mm
Table 5- 27
Terminal block X14, interface to the load
Connection
Signal
X14.1
BR L
X14.2
BR N
Max. connectable cross-section 2.5 mm
Danger to life if the permissible cable length of the brake control is exceeded
If the permissible cable length of the brake control is exceeded this can result in death or
serious injury in the event of an error.
• The maximum permissible cable length of 300 m between the 230 VAC Safe Brake
• To accurately calculate the maximum cable length, see the SINAMICS Low Voltage
Safety Integrated
Function Manual, 07/2016, A5E03264275A
WARNING
Adapter and the brake must be carefully maintained.
6SL3060-4DX04-0AA0 is used.
Description
Supply voltage: 230 VAC
Current consumption: 2 A
Protection according to IEC 60269-1, operating class gG
2
Description
Supply voltage: 230 VAC
Current consumption: 2 A, only for brakes with brake rectifier
2
WARNING
Adapter and the brake must be carefully maintained.
Configuration Manual on the customer DVD supplied with the device.
Controlling the safety functions
5.4 Activating "SBC" via the Safe Brake Adapter
93