Use Of The K82 Option With Control Unit Cu320-2 - Siemens SINAMICS Series Function Manual

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Figure 5-2
A switch according to ISO 13850/ EN 418, positive opening according to EC 60947-5-1, or a
certified safety controller must be used as actuating element.
5.2.2.2

Use of the K82 option with Control Unit CU320-2

In conjunction with option K90 or K95 (CU320-2 DP or CU320-2 PN), terminal -X41:10 is
already connected inside the cabinet with digital input DI 7 of the CU320-2.
In the Double Motor Module, digital input DI 6 is also wired on the CU320-2.
These interconnections have to be taken into account when Safety function parameters are
assigned.
Safety Integrated
Function Manual, 07/2016, A5E03264275A
5.2 Control of "STO" and "SS1" via terminal module for option K82
Circuit Terminal Module for option K82
Controlling the safety functions
43