System Storage Requirements; Grounding; Power Connection - Hitachi G1500 Hardware Manual

Virtual storage platform
Hide thumbs Also See for G1500:
Table of Contents

Advertisement

The weight for a fully configured 2-controller, 6-rack storage system can reach 6,146
pounds / 2,917 kilograms. The exact weight of the equipment depends on the storage
system configuration. The following table provides weights of typical system
configurations.
Note:
The data in the following table was taken from measurements of a system in
a controlled environment.
To calculate the power draw, current draw, and heat output of a specific
system, see
page 146)
URL: http://www.hds.com/go/weight-and-power-calculator.
Contact technical support if you need assistance using this tool.

System storage requirements

If the equipment must be stored after delivery and prior to installation, the storage
location must meet the storage environmental requirements for the storage system. See
Environmental specifications (on page 143)

Grounding

The site and site equipment must meet the following grounding requirements:
An insulated grounding conductor that is identical in size and insulation material and
thickness to the grounded and ungrounded branch-circuit supply conductors. It must
be green, with or without yellow stripes, and must be installed as a part of the branch
circuit that supplies the unit or system.
Connect the grounding conductor to earth ground at the service equipment or other
acceptable building earth ground. For a high rise steel-frame structure, this can be the
steel frame.
The receptacles in the vicinity of the unit or system must include a ground
connection. The grounding conductors serving these receptacles must be connected
to earth ground at the service equipment or other acceptable building earth ground.

Power connection

The AC power input for the storage system has a duplex PDU structure that allows the
rack-installed equipment to remain powered on if power is removed from one of the two
power distribution panels (PDP).
For more information, see
units for Hitachi Universal V2 Rack (on page 153)
Note: Site power can be connected to the PDUs at either the top or bottom of
the racks.
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide
Component weight_ heat_ airflow_ and power consumption (on
or (easier) use the weight and power calculator at the following
Electrical specifications (on page 140)
Chapter 4: Site preparation specifications
System storage requirements
for more details.
and
.
Power distribution