Filter Checking And Cleaning - Sungrow SG2500U-MV System Manual

Mv turnkey station
Table of Contents

Advertisement

System Manual
Fan
Device
maintenance
Safety function
Software
maintenance
LCD time display
Firefighting device
Other devices
The frequency of maintenance operations could be increased according to the
environmental conditions of the place where the MV Station is suited, plant
capacity and on-site situations.
The maintenance interval should be shortened if the sand or dust deposition
around the operation site is serious.

12.2.3 Filter checking and cleaning

It is recommended to check and clean the MV Station filter at least every six
months.
The maintenance interval should be shortened to once every three months or
shorter if the dust deposition is heavy.
The air inlets located on the front and back sides of the MV Station are entrances of cool air.
Periodically clean and replace the filter cotton and filter screen to ensure the air circulation
and proper temperature inside the MV Station.
Cleaning and replacing operation are performed on the air inlet window outside the MV
Station:
Push the two spring lock catches toward the middle of the air inlet window to open the
Step 1
outside shutters of air inlet window.
Check the running state of the fan inside the MV
Station
Check if there is crack in the fan blade
Check if there is abnormal noise during the running
of the fan;
 Routine check the corrosion of the metal
components (once six months)
 Annually check the contactors (auxiliary switches
and
micro-switches)
operation
 Check the running parameters (esp., voltage and
insulation)
 Check the emergency stop button and the LCD
stop function;
 Simulation shutdown
 Check the warning labels and other markings for
damage or unclearness. Replace them if necessary
 Optimize software
 Check each parameter setting
 Check if the time displayed on the LCD display is
correct;
 Replace the button cells on the back of the LCD
panel if time is incorrect after calibration.
Check the functionality of the firefighting devices
Replace the damaged lighting devices in time
to
ensure
the
optimal
12 Routine Maintenance
Every
six
months
or
maintain
according
to
real situation
From every six
months
to
annually
From every six
months
to
annually
From every six
months
to
annually
From every six
months
to
annually
Follow
related
regulation
where
the
project
is
located
When
necessary
87

Advertisement

Table of Contents
loading

Table of Contents