Burner Ignition Characteristics
Note: Connect gas supply and verify that the minimum inlet and outlet pressures are conforming.
Once the conversion to LPG and all the above steps have been completed, light the main burners.
Main burner should now light IMMEDIATELY and flame should not "lift" off burner. If there is any delay in ignition or if flame is
"lifting off" burner, turn off burner and carefully check for proper installation of logs/coals, vent system and proper pilot flame
impingement on burner. Logs or coals must not block pilot flame or main burner flame. Vent system must be leak proof.
WARNING: Do not proceed with operation of this fireplace unless burner "cycles" on/off without delays!
Pilot Flame and Burner Relationship Verification
Prior to completing the LPG conversion process, the qualified service technician must light the pilot light and verify the
relationship between the pilot light flames and the main burners. The pilot light flames directed towards the propagation ports
on the rear and front burner must overlap the propagation ports on the burners.
The pilot light flames must be a minimum of 1" long and must overlap the propagation ports on both the
rear and front burner legs. Verify that the burner tubes ignite quickly and the burner flames propagate
smoothly along the entire length of the burner.
85-03-01115
DXV35 TIMBERFIRE
Page 53