INTRODUCTION

Thank you for purchasing the Fuji Electric temperature/process
controller. All of these controllers are PID Autotune controllers that
employ Fuji Electric's patented fuzzy logic algorithms.
It is a fully programmable temperature/process controller incor-
porating many user-friendly features. The following easy-to-use
instructions are intended to help you understand, set up, effectively
operate, and achieve optimal performance from your controller. When
programmed and operated within the guidelines set up for them in this
manual, your controller will give you years of precise, reliable control.
If needed, we will provide free technical support throughout the life of
the controller.
The first section of this manual details the specifications and
general description for the PXV3 controller. The second section will
cover the PXW controller, followed by a detailed description of the
programming parameters, which are common to both the controllers.
Several appendices describe some of the controlling techniques.
Finally, a Quick Reference guide gives a listing of all the parameters
and their default values.

FEATURES

• Fuzzy Logic Control
• PID Autotune with manual override - heating or cooling
• Programmable control action - reverse or direct
• Programmable cycle time
• Programmable inputs - Thermocouple/ RTD, Current/ Voltage
• Sensor burn-out protection
• Input calibration by user
• Outputs: Relay, Solid-state relay drive, or 4-20mA DC (4-20mA not
available on PXV3)
• Secondary output for
cooling (optional)
• High/low alarm
outputs (optional)
• Heater break alarm (optional)
(only on PXW 5,7,9)
• Menu driven format
• Setting – touch keys on front panel
• Programmable 8-segment ramp/soak function
• Digital filtering (to suppress factory noise)
• Adjustable setpoint range
• Selectable °F/°C
• Offset adjustments
• Programmable decimal point
• Programmable lock feature
• Advanced security options to prevent unauthorized parameter
changes
• 4-digit, LED indication
• Output status indication
• Fault indication
• Non-volatile memory
• 1/32, 1/16, 1/8, 1/4 DIN and 72mm panel mount package
• NEMA 4X faceplate
• ABS plastic housing
• Termination— screw-down type (PXV3, PXW-5, 7, 9) or socket with
screw-down terminals (PXW-4)
• Metal mounting bracket; plastic bracket for PXV3/PXW-4
• 85 to 264V AC free voltage power supply
• 24V AC/DC power supply (optional)
• UL, C-UL, and CE approvals
• 3-year warranty

SAFETY PRECAUTIONS

Before using this product, the user is requested to read the follow-
ing precautions carefully to ensure safety. The safety requirements
are classified as either "warning" or "caution" according to the
following explanations:
suggesting that the user's mishandling can
Warning
result in personal death or serious injury.
suggesting that the user's mishandling can result
Caution
in personal injury or damage to the property.
Warning
Wiring
1. If there is danger of serious accident resulting from a failure or
defect in this unit, provide the unit with an appropriate external
protective circuit to prevent an accident.
2. The unit is normally supplied without a power switch or a fuse.
Use power switch and fuse as required (Rating of the fuse: 250V,
1A)
Power supply
1. Be sure to use the rated power supply voltage to protect the unit
against damage and to prevent failure.
2. Keep the power off until all of the wiring is completed so that
electric shock and trouble with the unit can be prevented.
General
1. Never attempt to disassemble, modify, or repair this unit.
Tampering with the unit may result in malfunction, electric
shock, or fire.
2. Do not use the unit in combustible or explosive gaseous atmos-
pheres.
Caution
Installation
1. Avoid installing the unit in places where:
• the ambient temperature may reach beyond the range of -10 to
50°C (14 to 122°F) while in operation
• the ambient humidity may reach higher than 90% RH while in
operation
• a change in the ambient temperature is so rapid as to cause
condensation
• corrosive gases (sulfide and ammonia gas, in particular) or
combustible gases are emitted
• the unit is subject to vibration or shock
• the unit is likely to come in contact with water, oil, chemicals,
steam, or vapor
• the unit is exposed to dust, salt, or air containing iron particles
• the unit is subject to interference with static electricity, mag-
netism,
or noise
• the unit is exposed to direct sunlight
• heat may be accumulated due to radiation
Maintenance
1. Do not use organic solvents such as alcohol or benzene to wipe
this unit. Use a neutral detergent.
2. Three-year warranty is guaranteed only if the unit is properly
used.