2.7

INJECTION SOURCE CONNECTIONS

The washer control may be programmed to send ten 120VAC output
signals for 60Hz models (or 24VAC for 50Hz) for a chemical injection
system. The signals are not intended as a power source and must be
limited to less than 100 milliamps of current. There is a separate terminal
block for connection of the external injection signals. For the injection
sources, program codes 1 through 10 and their respective terminal block
connections are as shown in Table 1.
Table 1: Injection Signal and Circuit Identification
If required, chemical injection hoses are to be inserted into the injection
inlet at the upper right rear of the washer. These hoses should be
inserted into the round PVC pipe a distance of:
For T-450 minimum of 8" (20 cm) and a maximum of 12" (30 cm)
For T-650, 750, 950 and 1450 a minimum of 14" (36 cm) and a maximum
of 18" (46 cm)
(For T-350 insert hoses into the top soap dish)
This will eliminate chemical buildup in the pipe and/or restrict water flow
to the tub. Secure the hoses as required.
8514-290-001 REV B page 21
Dexter
Controller /
Recommended
Injector
Connections
Signals
Detergent
Bleach
Starch
Sour/Softener
1
2
3
4
5
6
7
8
9
10