You have entered all of the data that is necessary for the basic commissioning of your
inverter.
SINAMICS G110M Getting Started
Getting Started, 09/2014, FW V4.7, A5E31298643B AC
Select the pre-assignment of the inverter interfaces.
The possible configurations can be found in sections: Factory setting of
the inverter control (Page 66) and Wiring example for the factory set-
tings (Page 64).
Select the application for the inverter:
Low overload for applications that only require a low dynamic perfor-
mance, e.g.: pumps or fans.
High overload for applications requiring a high dynamic performance,
e.g. conveyor systems.
Select your motor.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its order number, the data has
already been entered.
If you have set the "Vector control" control mode, then we recommend
setting "[1] Identify motor data at standstill and with motor rotating".
With this setting,
the inverter opti-
mizes its speed
controller.
If one of the following cases is applicable, select the setting "[2] Identify
motor data at standstill":
• You have selected "Vector control" as control mode; however, the
motor cannot freely rotate, e.g. for mechanically limited traversing
sections.
• You have set "V/f control" as control mode.
Set the most important parameters to suit your application.
Set the check mark for "RAM to ROM (save data in the drive)" in
order to save your data in the inverter so that it is not lost when the
power fails.
Exit basic commissioning.
4.8 Basic commissioning with STARTER
Commissioning
83