Siemens SINAMICS G110M Getting Started page 38

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Installation
3.2 System Installation
Connect the EM brake cables to the EM brake terminals
1. Connect the EM brake cables to the EM brake terminal block.
2. Connect the EM brake cables to the EMB+ and EMB- terminals
on the terminal block.
Notes:
Ensure that the cable is routed under the cable clamp.
The terminals can accept cable to a maximum size of 4 mm
The EM brake is an optional extra which is ordered separately.
7.
Connect the motor temperature sensor
1. Connect the motor temperature sensor cables to the temperature
sensor terminal block.
2. Ensure that the cable is clear of any obstructions and does not
restrict access to other cables and connectors within the terminal
housing.
Connect the motor temperature sensor (second part)
1. Connect the second part of the motor temperature sensor cable
to the temperature sensor terminal block.
2. The connector on the second part of the motor temperature sen-
sor is plugged into the Communications and Power Interface
(CPI).
Notes:
The motor temperature sensor terminal block has a diameter of
2.79 mm.
The final connection of the temperature sensor cannot be com-
pleted until the CPI has been fitted. This will be done after the
CPI is fitted, as shown later in this procedure.
38
.
2
SINAMICS G110M Getting Started
Getting Started, 09/2014, FW V4.7, A5E31298643B AC

Advertisement

Table of Contents
loading

Table of Contents