Appendix

13.5 Technical data

Inputs
Sensor inputs and
binary inputs
Other inputs
Outputs
Control signal y
Binary outputs
Interfaces
Operating voltage
Ambient temperature
Degree of protection
Class of protection
Degree of contamination 2 according to VDE 0110
Overvoltage category
Humidity rating
Noise immunity
Noise emission
Weight
116
EB 5474 EN
Max. 17 configurable inputs for sensors (Pt 100, Pt 1000, Ni 200, Ni
1000, PTC, NTC or 0-20 mA, 4-20 mA) or binary alarms
2 analog inputs 0-10 V, R
Three-step signals: Load 250 V~, 2 AC
On-off signals: Load 250 V~, 2 AC
Continuous control signal: 0 to 10 V, permissible load > 4.7 kΩ
6 outputs to control pumps and valves,
load max. 250 V~, 2 AC
2 outputs for alarms,
load max. 50 V~, 100 mA
Serial RS-232 interface for connection of a modem;
interface for meter bus
230 V, 48 to 62 Hz, output 8 VA
Permissible: 0 to 40 °C · Storage: –20 to 60 °C
IP 40 according to IEC 529
II according to VDE 0106
II according to VDE 0110
F according to VDE 40040
According to EN 61000-6-1
According to EN 61000-6-3
Approx. 0.6 kg
= 18 kΩ