Samson TROVIS 5474 Mounting And Operating Instructions page 121

Automation system 5400, boiler controller
Table of Contents

Advertisement

Public holidays
PA2
Date
Public holidays
PA3
Date
PA4: DHW heating
Parameters
Boiler set point for DHW demand
DHW demand ON
DHW demand OFF
Hysteresis
Function block parameters Co4
Maximum limit for DHW forced
charging (Fb02 = ON)
Day of week (Fb08 = ON)
Disinfection temperature
(Fb08 = ON)
Start time (Fb08 = ON)
Stop time (Fb08 = ON)
Times-of-day (only systems Anl 1 to 3 with Co5 -> Fb13 = ON)
Times-of-day
Monday (1)
Tuesday (2)
Wednesday (3)
Thursday (4)
Friday (5)
Saturday (6)
Sunday (7)
Start – Stop (1)
Appendix
Range of values
20 to 120 °C
20 to 90 °C
20 to 90 °C
0 to 30 °C
0 to 120 °C
0, 1 to 7, 1–7
50 to 80 °C
0:00 to 23:59
0:00 to 23:59
Start – Stop (2)
121
EB 5474 EN