3

Manual operation

All the settings of the outputs can be set in the manual mode, see wiring plan (-> section 12).
Proceed as follows:
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1
Note!
In manual mode, frost protection does not function.
Set mode selector switch to
After approx. 10 seconds the boilers start operation at
full capacity. Display:
Select HAnd on the display.
15
16
17
18
19
20
21
22
23
24
Open the manual level. Display: bA1
Select output:
Activate editing mode for output.
The display blinks.
Activate output, increase value.
Three-point stepping output: OPEN
or:
Deactivate output, decrease value.
Three-point stepping output: CLOSED
and:
Confirm setting.
The changed values remain valid as long as the manual
mode is active.
Slide mode switch to
bA: 1, 2
BA1 and BA2
3-Pt: 1, 2
BA3 and BA4, BA5 and BA6
PU: 1, 2
BA7 and BA8
StUF: 1, 2, 3, 4 BA9 to BA12
AnAL: 1, 2
AA 1, 2 (RK1, RK2)
Three-point stepping output: STOP
Exit the manual level.
Manual operation
.
.
EB 5474 EN
25