Technical Information
PLUS+1® MC0XX-1XX Controller Family
Inputs/outputs types and specifications
10 |
©
Danfoss | April 2018
A/D refresh rate
PLUS+1
®
module
MC012-110/112
MC024-110/112
MC024-120/122
MC050-110/112
MC050-120/122
MC050-155/15B
IOX012-110
IOX024-120
AIN/Temp/Rheo; Din/AIN/FreqIN/Rheo
Analog/Temperature/Rheostat (AIN/Temp/Rheo);
Digital/Analog/Frequency/Rheostat (Din/AIN/FreqIN/Rheo)
When configured as a resistance/rheostat/temp sensor input, the device will provide up to 3.76 mA
current to an external load which can then be measured. The equation for calculating AD counts for a
given load is: AD counts = (30996 x RL / (RL + 1322)). The following chart shows the relationship between
AD counts and load.
Rheostat inputs
The following chart shows the relationship between load resistance versus worst case error over the full
operating temperature -40° C to 70° C (-40° F to 158° F).
A/D refresh rate
All: 1.00 ms
All: 1.00 ms
All: 1.00 ms
All: 1.00 ms
All: 1.00 ms
All: 1.00 ms
Refresh rate is a function of CAN message frequency
Refresh rate is a function of CAN message frequency