PWM Max cycle
Comp. 1 Sd temp.
Comp. 1 Sd max.

Compressor timers

Lead comp. Min ON
Lead comp. Min OFF
Lead comp. Restart
Lead comp. Safety
delay
Comp. Min ON
Comp. Min OFF
Comp. Restart
Comp. Safety delay
Compressor status
Comp. 1 Sd gas
Comp. 1 status
Comp. 2....
Compressor capacity
Comp. 1 cap
Comp. 2......

Compressor runhours

Reset runtime
Comp.1 Runtime L
Comp.2.....
Compressor service
Comp.1 out of service The compressor can be taken out of operation, so that the controller regulates without this
Comp.2.....
AK-PC 351
For scroll
Limitation of capacity during time period. There is no limit if the setting in 100%.
For "Scroll" and "Stream"
Define whether the controller should monitor the discharge gas temperature Sd from a
digital scroll or a stream compressor (NTC 86K or Pt 1000 Ohm).
For scroll and Stream and yes to "Comp.1 Sd temp"
Set the maximum Sd temperature
Compressor timers
Min. On-time for first compressor
Set a forced On-time here during which the compressor will remain in operation before it
can be switched off again. The setting is to prevent incorrect operation.
To prevent a compressor breakdown, the setting must be made in accordance with the
requirements of the compressor supplier.
Min. Off-time for first compressor
Set the forced Off-time during which the compressor must be off before it can be switched
on again. The setting is to prevent incorrect operation.
Min. period of time for re-starting the first compressor.
Set the forced Off-time during which the compressor must be off before it can be switched
on again. The setting is to prevent incorrect operation.
To prevent a compressor breakdown, the setting must be made in accordance with the
requirements of the compressor supplier.
Delay time before compressor no. 1 cut out for reasons of safety
The time begins when a signal is received on the safety input for the compressor
Min. On-time for remaining compressors
Set a forced On-time here during which the compressor will remain in operation before it
can be switched off again. The setting is to prevent incorrect operation.
Min. Off-time for remaining compressors
Set the forced Off-time during which the compressor must be off before it can be switched
on again. The setting is to prevent incorrect operation.
Min. period of time for restarting remaining compressors
Set the forced Off-time during which the compressor must be off before it can be
switched on again. The setting is to prevent incorrect operation.
Delay time before compressors cut out for reasons of safety
The time begins when a signal is received on the safety input for the compressor
Compressor status
Read the Sd temperature of the compressor here.
Read the operating status for compressor 1 here. The following information may appear:
Power up=startup. Off= compressor stoppt. Manual ctrl=compressor manual controlled.
Cut out on safety=stoppt due to signal on DI-input. Restart timer=await timeout of time
delay. Ready=ready to start. Min OFF timer=await time out of time delay. Min. ON timer=await
timout of time delay. Full load=compressor works 100%. Running=compressor running.
Disabled=stoppt due to service
The same function for the remaining compressors
Compressor capacity
Read the connected capacity of the compressor (0-100%) here
The same function for the remaining compressors
Compressor run hours
Reset all of the hour counters and start counters for the subsequent compressors here.
Read the total operating time of the compressor (in hours) here
The same function for the remaining compressors
Compressor service
compressor.
No = Normal regulation
Yes = Regulating is carried out without this compressor, and no alarms are generated by it.
The same function for the remaining compressors
User Guide RS8GZ302 © Danfoss 2015-06
Min: 60%
Max: 100%
Fac: 100%
AI-demand
No / Yes
Fac: No
Min: 0°C
Max: 195°C
Fac: 125°C
Min: 0 min
Max: 60 min
Fac: 0 min
Min: 0 min.
Max: 30 min
Fac: 0 min
Min: 1 min.
Max: 60 min
Fac: 4 min
Min: 1 min.
Max: 10 min
Fac: 1 min
Min: 0 min.
Max: 60 min
Fac: 0 min
Min: 0 min.
Max: 30 min
Fac: 0 min
Min: 1 min.
Max: 60 min
Fac: 4 min
Min: 1 min.
Max: 10 min
Fac: 0 min
Yes /No
Fac: No