Using Isolated Dc Logic Modules In Marine Applications - Allen-Bradley 2711P Technical Data Manual

Wiring and grounding guidelines
Table of Contents

Advertisement

16
Wiring and Grounding Guidelines for PanelView Plus Terminals
PanelView Plus 700 to 1500 or
PanelView Plus Compact 1000 DC Terminals
Earth/Ground to Ground Bus
PanelView Plus 6 DC Terminals (700 to 1500)
Earth/Ground to Ground Bus
4. Apply 24V DC power to the terminal.
Figure 7 - DC Power Connections
3-position Terminal Block
(Series A - D Logic Modules)
+
DC - DC +
2-position Terminal Block
(Series E or Later Logic Modules)
+
GND
DC - DC +
2-position Terminal Block
Series A or Later Logic Module
GND

Using Isolated DC Logic Modules in Marine Applications

Isolated DC logic modules that are marine certified require a line filter for use in
marine applications. Use Corcom 6VW1 or equivalent filter type.
Earth/Ground
GND to Ground Bus
DC-
DC+
Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011
PanelView Plus 400/600 or
PanelView Plus Compact 400/600 DC Terminals
+
DC - DC +
PanelView Plus Terminal
With a Marine-certified
Logic Module
GND
DC- DC+
Line
Filter
Earth/Ground
GND to Ground Bus
+
DC +
DC -
Functional Earth
to Ground Bus
1 m (39 in.) maximum