Symptom
The PLC value is not equal to the
displayed value (regardless of
actual material level).
If you continue to experience problems, go to our website at:
www.siemens.com/processautomation, and check the FAQs for SITRANS LR200, or
contact your Siemens Milltronics representative.

Device Status Icons

Priority
Icon
Level
1
2
3
1
2
3
1
2
Page 94
SITRANS LR200 (PROFIBUS PA)– INSTRUCTION MANUAL
• Confirm you are looking at the right spot in the PLC.
• Ensure scaling has not been programmed into the
PLC: all scaling should be performed by the LR200.
• Check the network to ensure the PCL is
communicating with the LR200.
Meaning
• Maintenance alarm
• Measurement values are not valid
• Maintenance warning: maintenance demanded immediately
• Measured signal still valid
• Maintenance required
• Measured signal still valid
• Process value has reached an alarm limit
• Process value has reached a warning limit
• Process value has reached a tolerance limit
• Configuration error
• Device will not work because one or more parameters/components
is incorrectly configured
• Configuration warning
• Device can work but one or more parameters/components is
incorrectly configured
Corrective action (cont' d )
7ML19985JR01