Approvals

The device nameplate lists the approvals that apply to the device.
Note:
• General
• Radio
• Hazardous
• Marine

Programmer (infrared keypad)

Siemens Milltronics Infrared IS (Intrinsically Safe) handheld programmer for hazardous
and all other locations (battery is non-replaceable with a life expectancy of 10 years in
normal use).
• approval
• ambient temperature
• interface
• power
• weight
• color
• Part Number
1)
FM/CSA Intrinsically Safe connection drawing number 23650529 can be downloaded from
the product page of our website at:
www.siemens.com/processautomation.
2)
FM/CSA Non-incendive Class 1, Div 2 connection drawing number 23650537 can be down-
loaded from the product page of our website at:
www.siemens.com/processautomation.
7ML19985JR01
SITRANS LR200 (PROFIBUS PA) – INSTRUCTION MANUAL
CSA
, FM, CE
US/C
Europe: R&TTE
US: FCC
Canada: Industry Canada
1)
Intrinsically Safe
:
(Europe)
(US/Canada) FM/CSA: (barrier required)
(Australia)
(International) IECEx TSA 05.0009X Ex ia IIC T4
2)
Non-incendive
: (US)
Lloyd's Register of Shipping
ABS Type Approval
ATEX II 1 G, EEx ia IIC T4, certificate SIRA
01ATEX2147
FM/CSA: Class I, Div. 1, Groups A, B, C, D
−20 to 40° C (−5 to 104° F)
proprietary infrared pulse signal
3 V lithium battery
150 g (0.3 lb)
black
7ML1930-1BK
ATEX II 1 G EEx ia IIC T4
Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
Class III T4
ANZEx Ex ia IIC T4 IP67
FM:
Class I, Div. 2, Groups A, B, C, D T5