Advertisement

5. Communication

5.1. Device Address

The address can be changed and locked from a remote master. See
Note:
Resetting the PROFIBUS address to 126:
address lock
The unique address of the device on the network (also called PROFIBUS address).
Values
To change Device Address via SIMATIC PDM:
a)
Open the menu Device – Set Address.
b)
Enter value in New Address field and click on Assign Address button.
To change Device Address via the handheld programmer:
Device Address (default: 126)
See

5.2. Remote Lockout

Enables or disables programming via the network and PDM.
Options

6. Security

6.1. Write Locking

Prevents any changes to parameters via PDM or the handheld programmer.
handheld
programmer
Values
In SIMATIC PDM, open the menu Device – Write Locking, and select On or Off.

7. Language

Selects the language to be used on the LCD.
Options
7ML19985JR01
SITRANS LR200 (PROFIBUS PA) – INSTRUCTION MANUAL
0 - 126. Default: 126
on page 26 for details.
*
Off (Remote operation enabled)
On (Remote operation disabled)
Range: 1 to 9999
*
2457 (unlock value)
any other value
*
English
German
French
Spanish
on page 129 for details on disabling the
Off (enables programming)
On
(disables programming)