Symptom
Reading erratic
Reading response
slow
Reads correctly but
occasionally reads
high when vessel is
not full
Level reading lower
than material level
7ML19985JR01
SITRANS LR200 (PROFIBUS PA) – INSTRUCTION MANUAL
Operation Troubleshooting (cont' d )
Cause
echo confidence weak
liquid surface vortexed
material filling
Fill Rate (2.2.6.2.) setting is
incorrect
• detecting close range
echo
• build up near top of
vessel or nozzle
• nozzle problem
• material is within Near
Range zone
• multiple echoes
processed
• vessel near empty and
low dK material
Action (cont' d )
• use Auto False Echo Suppression
(2.2.4.2.) and Auto Suppression
Range (2.2.4.3.)
• use foam deflector or stillpipe
• decrease Fill Rate (2.2.6.2.)
• relocate instrument to side pipe
• increase confidence threshold in
Echo Threshold (2.2.3.1.2.)
• re-locate SITRANS LR200
• increase measurement response if
possible
• clean the antenna
• use Auto False Echo Suppression
(2.2.4.2.) and Auto Suppression
Range (2.2.4.3.)
• decrease Near Range (2.2.3.5.1.)
(minimum value depends on
antenna type)
• raise the device
• ensureAlgorithm (2.2.3.1.1.) is set to
tF (trueFirst echo)
• ensure Material (2.2.1.2.) selection is
LIQUID LOW DK
• set Position (2.2.3.1.3.) to Hybrid
• check the setting for CLEF
(Constrained Leading Edge Fit)
Range (2.2.3.4.1.): see the table
below Propagation Factor (2.2.1.1.)
for recommended settings
Page 101