To request a profile via the handheld programmer:
Echo confidence
value
C:38 A:TF D:4.25
TVT curve
material
level
1
2
a)
In PROGRAM mode, navigate to LEVEL METER > DIAGNOSTICS (3.) > ECHO
PROFILE (3.2)
b)
Press RIGHT arrow to request a profile.
c)
In the Profile screen, press UP Arrow to select the Transmit icon, and RIGHT
arrow to update the profile.
d)
Press DOWN Arrow to select the Exit icon, then RIGHT arrow to return to
previous menu.return to previous menu.

3.3. Measured Values

To access the following parameters via SIMATIC PDM, open the menu View – Peak
Values, and click on the appropriate tab.
3.3.1. Min. Measured Value
The minimum recorded Sensor value, defined in Sensor units.
3.3.2. Max. Measured Value
The maximum recorded Sensor value, defined in Sensor units.
3.3.3. Min. Output Value - AIFB1
The minimum recorded Output Value from Analog Input Function Block 1.
3.3.4. Max. Output Value - AIFB1
The maximum recorded Output Value from Analog Input Function Block 1.
3.3.5. Min. Output Value - AIFB2
The minimum recorded Output Value from Analog Input Function Block 2.
3.3.6. Max. Output Value - AIFB2
The maximum recorded Output Value from Analog Input Function Block 2.
3.3.7. Min. Internal Temperature
The minimum recorded electronics temperature of SITRANS LR200.
3.3.8. Max. Internal Temperature
The maximum recorded electronics temperature of SITRANS LR200.
Page 70
SITRANS LR200 (PROFIBUS PA) – INSTRUCTION MANUAL
Algorithm selection (trueFirst echo)
Distance value
3
4
5
transmit icon, deselected
exit icon, selected
transmit icon,
selected
exit icon,
deselected
7ML19985JR01