c. That the joint tightness is correct for the joint material
used.
d. That only suitably certified cable entry devices will be
utilized when connecting this equipment.
e. That any unused cable entries are sealed with suitably
certified stopping plugs.
9. The probe fork is subjected to small vibration stresses as part
of its normal function. As this provides a partition wall, it is
recommended that the fork should be inspected every two
years for signs of defects.
10. Technical data:
a. Coding: Class 1, Div 1, Groups A, B, C, and D
b. Temperature: See
c. Pressure: Must not exceed the rating of the
coupling/flange fitted.
d. For electrical details and pressure ratings, refer to
"Specifications" on page
e. Year of manufacture: Printed on product label.
Table B-1. High temperature Rosemount 2130
2130**9E***********E5***,
2130**9E***********E6***:
Temperature
ambient air
classes
temperature (Ta)
T6, T5, T4, T3, T2, T1
T5, T4, T3, T2, T1
T4, T3, T2, T1
T3, T2, T1
T2, T1
Minimum ambient air temperature (Ta) = –50 °C
Minimum process temperature (Tp) = –70 °C
Table B-2. Medium temperature Rosemount 2130
2130**9M***********E5***,
2130**9M***********E6***:
Temperature
ambient air
classes
temperature (Ta)
T6, T5, T4, T3, T2, T1
T5, T4, T3, T2, T1
T4, T3, T2, T1
T3, T2, T1
Minimum ambient air temperature (Ta) = –40 °C
Minimum process temperature (Tp) = –40 °C
Product Certifications
Table B-1
or
Table B-2
39.
Maximum
Maximum
process
temperature (Tp)
75 °C
80 °C
74 °C
95 °C
73 °C
125 °C
69 °C
185 °C
65 °C
260 °C
Maximum
Maximum
process
temperature (Tp)
75 °C
75 °C
70 °C
90 °C
65 °C
125 °C
50 °C
180 °C
11. Cable selection:
a. It is the responsibility of the user to ensure that
suitably temperature rated cable is used.
Table B-3
below is a guide to selection.
Table B-3. Cable Selection (E5 and E6)
T Class
T6
T5
T4
T3
Note
A certified isolating amplifier to IEC 60947-5-6 is required
for intrinsic safety if the NAMUR electronics is used in a
hazardous area installation (see below).
A certified intrinsically safe barrier is required for intrinsic
safety if the 8/16 mA electronics is used in a hazardous area
installation (see below).
Factory Mutual (FM)
intrinsically safe and non-incendive approvals
I5
Project ID: 3011456
Intrinsically Safe for Class I, Div. 1, Groups A, B, C, and D
Class I, Zone 0, AEx ia IIC
Non-incendive for Class I, Div. 2, Groups A, B, C, and D
Class I, Zone 2, IIC
Temperature Code: T5 (See Control Drawings)
Control Drawing: 71097/1154 (with NAMUR electronics)
(Figure B-1 on page
57)
Vmax=15 V, Imax=32 mA, Pi=0.1 W, Ci=211 nF, Li=0.06 mH
Control Drawing: 71097/1314 (with 8/16 mA electronics)
(Figure B-2 on page
58)
Vmax=30 V, Imax=93 mA, Pi=0.65 W, Ci=12 nF, Li=0.035 mH
See
also"Instructions for hazardous (classified loc.) area
installations (I5 and I6)" on page
Canadian Standards Association (CSA)
intrinsically safe and non-incendive approvals
I6
Certificate Number: 06 CSA 1786345
Intrinsically Safe for Class I, Div. 1, Groups A, B, C, and D
Class I, Zone 0, Ex ia IIC
Non-incendive for Class I, Div. 2, Groups A, B, C, and D
Temperature Code: T5 (See Control Drawings)
Single Seal
Control Drawing: 71097/1179 (with NAMUR electronics)
(Figure B-3 on page
59)
Vmax=15 V, Imax=32 mA, Pi=0.1 W, Ci=211 nF, Li=0.06 mH
Control Drawing: 71097/1315 (with 8/16 mA electronics)
(Figure B-4 on page
60)
Vmax=30 V, Imax=93 mA, Pi=0.65 W, Ci=12 nF, Li=0.035 mH
See also
"Instructions for hazardous (classified loc.) area
installations (I5 and I6)" on page
Product Certifications
January 2019
Cable Temperature Rating
Above 185 °F (85 °C)
Above 212 °F (100 °C)
Above 275 °F (135 °C)
Above 320 °F (160 °C)
56.