2.7.4

Fault and alarm relays (2 x SPCO) electronics cassette

Figure 2-25. SPCO Fault and Alarm Relays (Light Green Label)
PE
(Ground)
Note
A DPST (Double Pole, Single Throw) on/off switch must be installed to safely disconnect the power
supply. Fit the DPST switch as close as possible to the Rosemount 2130. Keep the DPST switch free of
obstructions. Label the DPST switch to indicate it is the supply disconnection device for the
Rosemount 2130.
NC
(=No alarm)
LED on continuously
Installation
OPERATION MODE
WARNING
Seconds Delay
Dry On
Dry On
Wet On
Dry
N
L
0.3
0.3
Wet
1
1
3
3
10
10
Dry
30
30
Wet
Wet On
1
2
3
Fuse 0.5 (T)
DPST
U = 20...264 V ~ (ac)
N
Live
(50/60 Hz)
I < 6 mA
U = 20...60 V
0V
+V
I < 6 mA
High level, dry = on
Dry On
Wet On
0.3
0.3
1
1
3
3
10
10
30
30
Seconds Delay
C
NO
NC
C
NO
NC
(=Alarm)
(=No fault)
LED flashes every second
Isolate Supply
Alarm
Before Removing
NC
C
NO
NC
4
5
6
7
NC
C
NO
NC
Resistive Load
Inductive Load
cos φ = 1 ;
cos φ = 0.4 ;
L/R = 0 ms
L/R = 7 ms
I
I
= 5 A
MAX
MAX
ac:
ac:
U
U
= 250 V
MAX
P
P
= 1250 VA
MAX
dc:
dc:
U
U
= 30 V
(dc)
MAX
P
P
= 240 W
MAX
C
NO
NC
C
NO
NC
(=No alarm)
(=No fault)
LED on continuously
Fault
C
NO
8
9
C
NO
= 3.5 A
= 250 V
MAX
= 875 VA
MAX
= 30 V
MAX
= 170 W
MAX
Low level, wet = on
Dry On
Wet On
0.3
0.3
1
1
3
3
10
10
30
30
Seconds Delay
NC
C
NO
C
NO
NC
(=No fault)
(=Alarm)
LED flashes every second
Installation
January 2019
NC
C
NO
C
NO
(=No fault)
27