Battery Test And Charging Procedures - Cooper F6-PA-LS Installation And Operation Instructions Manual

Form 6-ls microprocessor-based pole mount recloser control
Table of Contents

Advertisement

Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Battery Test and Charging
Procedures
Test Procedure for Installed Battery
Follow the procedure below to perform a battery test in the
Form 6-LS control. The values in the test procedures are
based on testing at 25°C (77°F).
The condition of the Form 6-LS control battery can be
determined by using the Battery Test function in the
BATTERY MENU. No external current/voltage meter is
necessary for testing.
Alarm Conditions:
• During a manual battery test a 5Ω, 55 watt resistor is
placed across the battery terminals for approximately 5
seconds. The Form 6-LS control measures the battery
voltage, if the voltage drops below 22.8 VDC for one
full second, the ALARM LED (battery alarm) is
illuminated.
• When the Form 6-LS control is disconnected from AC
power and the control battery drops below 23.5 VDC
for 60 seconds, the ALARM LED will illuminate. If the
battery voltage continues to decay and drops below 22
VDC, the Form 6-LS control will shut down.
Note:
The battery test is blocked for 30 seconds upon power
up of the control.
Note:
AC power can be either connected or disconnected for
battery test.
Note:
If the battery voltage drops below 19V, the battery must
be charged by the external battery charger KA43ME7001.
1. Press the MENU button on the front panel.
2. Using the down arrow key, navigate to the BATTERY
menu and press ENTER.
3. Using the down arrow key, navigate to the TEST
BATTERY menu and press ENTER.
4. Press the F4 button to test the battery. The battery test
results will display in the battery metering menu.
Note:
Voltage should be between 25–31 VDC with the
higher voltage at colder temperatures.
Under normal conditions, with AC connected and a
fully charged battery, the charging current should be
less than 20 mA.
With AC connected and a discharged battery the
current range should be between 20 and less than
450 mA. Current of 450 mA or greater indicates a
problem with the charging circuit on the pole mount
power supply.
With AC disconnected and the battery supplying the
load, current will read -400 to -600 mA depending on
connected accessories.
TABLE 11
Control Battery Bench Testing and Replacement Information
Control Type
Form 6-LS (high capacity)
42
Test Procedure for Uninstalled Battery
The entire process should be conducted in a clean
environment, such as a repair shop.
Refer to Table 11 and follow this procedure to perform a
bench test on a control battery in a service shop:
1. Remove the control from service. Refer to Remove the
Control from Service procedure within the Testing
section of this manual.
2. Remove the battery from the control and carefully
transport it to a suitable service facility.
3. Measure battery voltage.
4. Apply test load and measure battery voltage after 5
seconds of load to determine voltage drop. Refer to
Table 11 for Bench Test Load Condition.
5. Remove test load.
If the battery fails the test or is at least four years old, it
should be replaced. Refer to Table 11 for battery catalog
part number.
Battery
Catalog
Part #
Voltage
Type
KME5-134-1
24v
Lead
(two
12v
batteries)
Bench
Test Load
Amp/
Condition
Hour
for 5 sec.
13
Acid
55 watt
Acceptable
Voltage Drop
at End of
Test Load
2v
or less

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F6-pb-ls

Table of Contents