Before Placing Control And Recloser Into Service - Cooper F6-PA-LS Installation And Operation Instructions Manual

Form 6-ls microprocessor-based pole mount recloser control
Table of Contents

Advertisement

Before Placing the Control and the
Recloser into Service
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until
all control settings have been properly programmed and
verified. Refer to the programming information for this
control. Failure to comply can result in control and
recloser misoperation, equipment damage, and personal
injury.
Prior to placing the control and recloser into service, the
following installation procedures must be properly com-
pleted and verified:
1. Front panel label inserts changed (if applicable).
Note:
Refer to Using Removable Inserts in this manual.
2. Control properly mounted for the installation.
3. Recloser installed according to all locally approved
standards and practices.
4. AC disconnect switches installed.
5. Control and recloser properly grounded in accordance
with guidelines in this manual and the applicable
recloser manual.
CAUTION: Equipment misoperation. Verify that
the 120/240 VAC selector switch is correctly set
for incoming voltage. Failure to comply may cause
misoperation (unintentional operation) of the control
and/or equipment damage resulting in personal injury.
CAUTION: Equipment damage Form 6-LS (Loop
Scheme). Do not connect 240 VAC to B or Y phases on
terminal blocks TB7 or TB8. 240 Volts will damage
internal components and cause control misoperation.
6. Control cable properly connected and supported.
7. Verify the selector switch on the Power Supply/Battery
Charger Board is set to the 115V position for 120 VAC
incoming power.
8. Control battery connected and tested for proper
operation.
Note:
The battery test is blocked for 30 seconds upon
power-up of the control.
Test the battery as follows:
A. Press the MENU button on the front panel.
B. Using the down arrow key, navigate to the BATTERY
menu and press ENTER.
C. Using the down arrow key, navigate to the TEST
BATTERY menu and press ENTER.
D. Press the F4 button to test the battery.
Note:
This message will appear on the programming
panel LCD display: ----TESTING----
The battery test results will display in the battery
metering menu.
Note:
With AC disconnected and the battery supplying
the load, current will read -400 to -600 mA
depending on accessories connected.
9. AC power connected to the control. (Control OK LED
G110.3
indicator is illuminated.)
Note:
The control Power Save feature will turn off the back-
lit LCD display and all LEDs if no front panel keypad
is pressed within ten minutes.
10. All control programming entered and verified by appro-
priate personnel.
Note:
Refer to Service Information S280-70-4 (ProView
4.X.X) or S280-70-21 (ProView 5.X.X) Form 6
Microprocessor-Based
Programming Guide for additional information.
IMPORTANT: Form 6-LS control users must activate
the loop scheme default settings in the ProView
application software Idea Workbench:
1. Click on LOAD IDEA WB STRUCTURE.
2. Select WBI-Form6-F6Default-LS.sch and click on
Open.
3. Click on READ IDEA WB SETTINGS FROM DISK.
4. Select WBI_Form6_Settings_F6 Default-LS.txt and
click on Open.
5. Enable the LS functionality by selecting the LS
T278.0
Enable checkbox in the Loop Scheme Settings
Dialog box located in the Idea Workbench Optional
Loop Scheme Workbench.
11. Control clock set to the correct time.
Note:
Refer to Service Information S280-70-4 (ProView
T314.0
4.X.X) or S280-70-21 (ProView 5.X.X) Form 6
Microprocessor-Based
Programming Guide for additional information.
12. Customer connections for remote and supervisory
operation checked and completed in accordance with
proper shielding and surge protection (Figure 19).
NOTICE: External leads must be shielded and the shield
must be grounded at both ends. Terminate each lead with
a 320VAC, 150 Joules metal oxide varistor (MOV), or
equivalent, at the remote end. Attach MOV's between the
leads and ground. Failure to properly shield and protect
leads can result in equipment damage and/or unintentional
operation.
S280-70-10
Recloser
Control
Recloser
Control
31