Recloser Vtc Interface - Cooper F6-PA-LS Installation And Operation Instructions Manual

Form 6-ls microprocessor-based pole mount recloser control
Table of Contents

Advertisement

Control-Powered Type NOVA reclosers with serial numbers
100,000 and above, as listed in Table 13, require a VTC-
ready control. They are equipped with a 19-pin control
cable receptacle and can be identified by labels prominently
displayed on the bottom of the recloser tank and on the
side near the 19-pin receptacle, as shown in Figure 38.
For more information on the Control-Powered NOVA
Interface, refer to Service Information S280-42-1
CAUTION:
Equipment
control-powered NOVA reclosers that require a
VTC interface must be used with VTC-ready controls.
Failure to use a VTC-ready control will result in failure to
trip or close.
TABLE 13
Serial Number Break for Control-Powered NOVA Reclosers
with VTC
Control-Powered NOVA
NOVA15
NOVA27
NOVA38
Note:
Control-powered NOVA reclosers with serial numbers
below those listed in Table 13 do not require a VTC-
ready control. Refer to the recloser nameplate for the
serial number.

RECLOSER VTC INTERFACE

Misoperation.
The
G144.0
Serial No.
100,000
100,000
100,000
Figure 38.
Receptacle side view and bottom view of NOVA
recloser tank, showing placement of VTC label.
S280-70-10
45