Ac Input Connector; Battery Connector; 12Vdc Auxiliary Power Terminals; Back Tamper Connector - Cooper Scantronic 95 Installation Instructions Manual

Hardwired control unit
Hide thumbs Also See for Scantronic 95:
Table of Contents

Advertisement

95 Installation Instructions

AC Input Connector

("14" in Figure 2.)
The two outer terminals of the AC IN connector connect to the 17VAC output
from the mains transformer.

Battery Connector

("15" in Figure 2.)
Note: Do not connect the battery until all other wiring has been completed.
The BATT terminals are for connection to a +12Vdc standby battery. A battery
lead is provided (red wire to "+").
12V Battery
If the mains power to the control panel fails, the standby battery will take over
and maintain the system. In order to safeguard the battery from full discharge,
the control panel automatically isolates the standby battery when its voltage
falls below 9.5V. When the mains power is restored, the system will power-up
and continue to recharge.
An MS1000 Battery Kit is required to fit a 17AH battery inside the cabinet.

12Vdc Auxiliary Power Terminals

("16" in Figure 2.)
You can use the terminal block in the bottom-left corner of the control panel
PCB to power devices such as PIR detectors. The terminals provide 12Vdc
(protected by a polyfuse). Refer to page 20 for power availability.

Back Tamper Connector

("17" in Figure 2.)
The BACK TAMPER connector should be wired to the "back tamper switch",
which is mounted on a plate that slides into slots shown in Figure 1. The
switch enables the system to generate a tamper alarm if the lid of the control
panel is removed or if the control panel is removed from the wall.
+
-

Figure 14. Battery Connections

11680293 Issue 1
2. Installation
+
_
Control Panel
battery terminals
Page 17

Advertisement

Table of Contents
loading

Table of Contents