Introduction

Service Information S280-70-10 provides installation and
operation instructions for the Form 6-LS pole mount
recloser control with loop scheme accessory.
Refer to the following information as appropriate for your
version of ProView software:
• Service Information S280-70-4 Form 6 Recloser
Control Programming Guide: ProView 4.X.X software
• Service Information S280-70-21 Form 6 Recloser
Control Programming Guide: ProView 5.X.X software
Read This Manual First
Read and understand the contents of this manual and
follow all locally approved procedures and safety practices
before installing or operating this equipment.
Additional Information
These instructions cannot cover all details or vari ations in
the equipment, procedures, or process described, nor
provide directions for meeting every possible contin gency
during installation, operation, or maintenance. When
additional information is desired to satisfy a problem not
cov ered sufficiently for the user's purpose, contact your
Cooper Power Systems sales representative.

ANSI Standards

Kyle reclosers are designed and tested in accordance with
the following ANSI standards: C37.60 and C37.85 and
ANSI Guide C37.61.

Quality Standards

ISO 9001-Certified Quality Management System

Acceptance and Initial Inspection

Each Form 6 recloser control is completely assembled,
tested, and inspected at the factory. It is carefully calibrated,
adjusted and in good condition when accepted by the
carrier for shipment.
Upon receipt, inspect the carton for signs of damage.
Unpack the control and inspect it thoroughly for damage
incurred during shipment. If damage is discovered, file a
claim with the carrier immediately.

Handling and Storage

Be careful during handling and storage of the control to
minimize the possibility of damage. If the control is to be
stored for any length of time prior to installation, provide a
clean, dry storage area. If storage is in a humid atmosphere,
make provisions to keep the control circuitry energized.
To energize the control, apply AC power to the AC supply
Note:
input terminal block located in the lower right hand
corner of the back panel of the control. Refer to the
Customer Connections for AC Power section in this
manual.

PRODUCT INFORMATION

Control Battery Storage and Charging
The 24 VDC control battery in the Form 6 recloser control is
fully charged prior to shipment and is ready for use.
Temperature has an effect on battery life. Sealed lead acid
batteries should be stored, fully charged, at room
temperature. Never store lead acid batteries at temperatures
exceeding 47°C (117°F), as damage can result in
approximately one month.
The batteries must be tested and charged for 24 hours
following every three months of storage from the last test
date. A separate portable charger accessory is available.
Catalog Number KA43ME7001 provides a 120 Volt battery
charger to power individual batteries.
Note:

Control Power

The Form 6-LS control is powered from 120 VAC. The
selector switch on the power supply board must be set to
the 115V position.

Battery Replacement and Disposal

The 24 VDC control battery has a life expectancy of four
years. It is recommended that the battery be replaced after
four years or if the battery fails a battery test - whichever
occurs first.
Note:
Dispose expired batteries in an environmentally responsible
manner. Consult local regulations for proper battery
disposal.
IMPORTANT: To maintain sufficient charge to operate
the control and prevent battery cell damage, the sealed
lead-acid batteries should be charged after no more than
three months of storage.
IMPORTANT: Connect the control battery before AC
power is connected to the control's AC supply Input
Terminal Block. The battery must be disconnected prior
to shipping or storing the control.
When shipped from the factory, the battery source is
disconnected and its output plugs are taped to the
cabinet. Connect the battery plugs into the mating
connectors to complete the battery circuit.
CAUTION: Equipment misoperation. Verify that
the 120/240 VAC selector switch is correctly set
for incoming voltage. Failure to comply may cause
misoperation (unintentional operation) of the control and/
or equipment damage resulting in personal injury.
CAUTION: Equipment damage Form 6-LS (Loop
Scheme). Do not connect 240 VAC to B or Y phases on
terminal blocks TB7 or TB8. 240 Volts will damage
internal components and cause control misoperation.
Battery life is decreased at higher temperatures.