General Parameters - Operating Mode - ABB i-bus KNX 6108/06-500 Technical Reference Manual

Push-button coupling unit, 2gang, 4gang
Table of Contents

Advertisement

Application "1-button operating mode "Setting "Adjust room temperature controller""

10.12.2 General parameters - Operating mode

NOTE
The options are dependent on the setting of the "Object type for output"
parameter.
Options:
The "Operating mode" parameter specifies the operating mode that is sent out on the 1-byte
communication object for the KNX operating mode switchover when a button is operated. The
possible selections are:
Auto (1 byte only)
Comfort
Standby
Eco
Frost protection, heat protection
With selection "Auto" the value "0" is sent out on the1-byte object. For a connected room
temperature controller, this means that for every new operation, the individual operating modes
"Comfort", "Standby" and "Night" will be switched between. When forced guidance is activated,
selection "Auto" is used to switch over to the standard operating mode object.
With the selection of "Comfort", a "1" is sent out on the 1-byte object and a connected room
temperature controller switches to the comfort operating mode.
With the selection of "Standby", a "2" is sent out on the 1-byte object and a connected room
temperature controller switches to the standby operating mode.
With the selection of "ECO", a "3" is sent out on the 1-byte object and a connected room
temperature controller switches to the night time temperature reduction operating mode.
With the selection of "Frost protection, heat protection", a "4" is sent out on the 1-byte object
and a connected room temperature controller switches to the frost/heat protection operating
mode.
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
Description of application and parameters
Auto (1 byte only)
Comfort
Standby
Eco
Frost protection, heat protection
│57