Omron ERT1 Series Operation Manual page 83

Ethernet/ip slave units
Table of Contents

Advertisement

Environment-resistive Slave Units
Indicators
Communications
Indicators
Input Indicators
Pin
1
V+ (24 V: for internal circuits and inputs)
2
NC
3
V− (0 V: for internal circuits and inputs)
4
NC
(4) Communications Indicators: MS and NS
These indicators show the Unit communications status and network commu-
nications status.
(5) Input Connectors
The input devices are connected to these connectors.
(6) Input Indicators
These indicators show the ON/OFF status of the inputs and the error status of
connected devices.
Refer to 3-1-3 Communications Indicators.
These indicators show the ON/OFF status of the inputs and the error status of
connected devices.
Indicator
Color
1-A
Lit yellow.
Not lit.
Lit red.
Flashing red.
1-B
Lit yellow.
Not lit.
Lit red.
Flashing red.
2-A
Lit yellow.
Not lit.
Lit red.
Flashing red.
2-B
Lit yellow.
Not lit.
Lit red.
Flashing red.
Signal
Status
Meaning (main error)
Input 0 is ON.
Input 0 is OFF.
Connector 1 is short-circuited.
Connector 1 is disconnected.
Input 1 is ON.
Input 1 is OFF.
---
---
Input 2 is ON.
Input 2 is OFF.
Connector 2 is short-circuited.
Connector 2 is disconnected.
Input 3 is ON.
Input 3 is OFF.
---
---
Section 5-2