Screw-less Clamp Terminals
I/O Indicators
Setting the Node
Address
Internal Circuits
Wiring
52
The meanings of the input indicators are given in the following table.
Indicator name
Status
0 to 15
I/O
The rotary switches are used to set the lower digits of the IP address.
Setting method
Two hexadecimal digits
Setting range
01 to FE
Rotary Switch Settings
00 hex:
BOOTP or tool setting enabled (factory setting)
01 to FE hex: Setting on rotary switches is lower 8 bits of IP address. (De-
fault setting of upper 24 bits: 192.168.250.)
FF hex:
Restores default setting.
(To restore the default setting, set the switches to FF hex, cycle the power
supply, and then set the switches to 00 hex.)
8
NC
7
NC
6
RD−
5
Pulse
NC
trans-
4
NC
former
3
RD+
2
TD−
1
TD+
DC-DC
V+
converter
(non-isolated)
V−
NC
0
1
2
3
4
V
V
V
V
V
V
G
G
G
G
G
G
Color
Yellow
Lit yellow when output is ON.
Red
Flashing red when the load is dis-
connected.
Automatically reset when the load
is connected.
Red
Lit red when the load is short-cir-
cuited.
Automatically reset when the
short-circuit is removed.
OFF
Not lit when output is OFF.
Green
Lit green when I/O power is being
supplied.
OFF
Not lit when I/O power is not being
supplied.
I/O indicator
Internal
circuits
disconnection
Photocoupler
5
6
7
8
9
10
V
V
V
V
V
V
G
G
G
G
G
G
Section 4-2
Meaning (main error)
V
V
G
G
Voltage
drop
Short-circuit
or
detection
0 to 15
circuit
V
G
11
12
13
14
15
V
V
V
V
V
G
G
G
G
G
NC
V
G