Commissioning

This chapter describes the commissioning of the gateway by using Profibus-DPV1/
SPA Configuration Tool (PCT).
The commissioning phase includes following actions in short:
1. Set the gateway to configuration mode.
2. Connect the PC containing the Profibus-DPV1/SPA Configuration Tool to the
gateway.
3. Open a standard configuration and define the SPA addresses and scaling. In a
multislave project, you can import several standard configurations to the
different slave sections in PCT. For more information, refer to Section 4.3.
Multislave configuration.
4. Save the configuration with a new name.
5. Download the configuration and, optionally, the source to the archive.
6. Connect the gateway to the protection relays and start it up.
7. Connect the gateway to the PC again and upload the configuration.
8. Verify that the appropriate In Use flags are checked.
See the following sections for details about the actions.

Hardware set-up

The gateway and the PC hardware must be connected and set up properly in order to
perform a successful configuration of the gateway.
If the ordered product package is a SPA-ZC 302-AA or BA, the provided connection
cable (1MRS120541) can be used for configuration purposes if a gender change
adapter (female-female) is used for the PC connection.
Connect the cable between the COM port on the PC and the SPA protocol port on
the gateway device. If your PC contains only USB ports, you need an USB to COM
port adapter, which can be purchased from any well-equipped computer store.
To RS-232 PC COM port
SPA
RS485
RS232
SPA-ZC 302
Off-line Acyclic
Address
Profibu
On-line Diagnostics
s
RS485
SPA INTERFACE
RS485 0000000 1111
TTL
0000011 0000
RS232 0111000 0000
+8V
1
gateway
SPA-ZC 302
EXTERNAL POWER
U aux
110...240VAC
110...220VDC
-
+
CE
N L
1 2
Fig. 4.1.-1 Configuration arrangement principle
The SPA protocol port setting must be set to RS-232 using the DIP switches as
described in Section 3.3.3.3. DIP switch configuration.