New Configuration - ABB SPA-ZC 302 Installation And Commissioning Manual

Profibus-dpv1/spa gateway
Table of Contents

Advertisement

SPA-ZC 302
4.2.
28
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
Ensure that PCT is set to use the serial port that the cable is connected to. Check this
by selecting Settings > COM in the main menu in PCT. For details about PCT, see
Section 5.2. Starting PCT. PCT adjusts the COM port settings of the PC
automatically.

New configuration

Before a new configuration is started, you have to select a standard configuration
template from the configurations described in Chapter 6. Standard configuration
templates. Which one you should select, depends on the requirements of the system
in which the protection relay and the gateway device are installed.
When you have selected the standard configuration template, you have to define the
protection relay dependent data and commission the gateway by following the
instructions below:
1. Start the PCT and open the selected standard configuration template by
selecting File > Open in the main menu. Select the wanted standard
configuration template and click Open, or just double-click on the template you
want.
Fig. 4.2.-1 Opening the configuration template
Define the address of the SPA slave connected to the gateway by selecting Slave >
Set Address and type in the address in the SPA Slave Address dialog,
see Fig. 4.2.-2.
Fig. 4.2.-2 Setting the SPA Slave Address
1MRS755014
A050341
A050295