SPA-ZC 302
32
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
2. Ensure that the correct COM port is selected from the Settings > COM menu in
PCT.
3. Also ensure that the gateway is in configuration mode. Configuration mode is
enabled by using the DIP switches on the front of the gateway, see Section
3.3.3.3. DIP switch configuration.
4. Select Device > Download configuration in the main menu. The configuration
is now downloaded and a confirmation dialog is displayed. Click OK to confirm
the download, see Fig. 4.4.-1.
Fig. 4.4.-1 Configuration download succeeded
This step is optional but it is a good practice to also download the configuration
source to the gateway. In this way the gateway always contains all the necessary data
that can be used in the future. The configuration archive can be downloaded as such
or compressed to a zip file. After that, select Device > Download Archive in the
main menu and a file selection dialog is opened. Select the saved configuration that
has been made for the gateway "<filename>.pcf" and click Open. When this is done,
the archive will be downloaded to the device and the a confirmation dialog is shown,
see Fig. 4.4.-2. Click OK to confirm the archive download. For more information
on LEDs, see Section 8.4. Troubleshooting.
Fig. 4.4.-2 Archive download succeeded
The archive is stored in the device until another archive is downloaded and the new
archive overwrites it.
5. In order to verify the signals that are actually read from the protection relay:
• The configuration is uploaded after the first start-up with the protection relay
connected.
• The state of the In Use flag is checked.
For details on how to do this, see Sections Section 4.7. In Use flags.
1MRS755014
A050353