Self-Diagnosis; Led Indicators - ABB SPA-ZC 302 Installation And Commissioning Manual

Profibus-dpv1/spa gateway
Table of Contents

Advertisement

SPA-ZC 302
8.3.
8.3.1.
Table 8.3.1-1
Profibus-DPV1 LED indicator
LED no Description
1
Acyclic
Traffic
2
Fieldbus
ON-line
3
Fieldbus
OFF-line
4
Fieldbus
Diagnostics
62
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual

Self-diagnosis

LED indicators

Fig. 8.3.1.-1
Profibus-DPV1 LED indicators
See Table 8.3.1-1 for the description of the Profibus LED indicators pictured in
Fig. 8.3.1.-1 .
Colour
State
On
Green
Off
On
Green
Off
Flashing 1 Hz
On
Red
Off
Off
Red
Flashing 1 Hz Error in configuration data.
Flashing 2 Hz Error in parameter data.
Flashing 4 Hz Error in initialising of the Profibus communication ASIC.
1
0
0
4
Indicates
A DPV1 request is currently being executed.
No Power to the module.
No DPV1 request is currently being executed.
Bus is on-line and data exchange is possible.
No power to the module.
Bus is not on-line.
Clear mode. The Profibus master has initiated a clear command.
Bus is off-line.
No power to the module.
Bus is NOT off-line
No power to the module.
No diagnostics is present.
2
3
ProfibusLED_a