3. Select the next tabbed page representing the second slave.
4. Select Slave > Import to open a dialog for importing the configuration
template, see Fig. 4.3.-3.
Fig. 4.3.-3 Importing the configuration template
5. In the Import dialog, select the configuration matching the second relay.
6. Select Slave > Set address to set the address of the second relay, see Fig. 4.3.-1.
7. Repeat these steps for all the slaves and always check the total template size
while adding slaves and importing their configurations.
After each import, remove the unnecessary data items. It helps you to keep total
template size under 240 bytes and removes unnecessary profibus traffic.
All the data included in the template is transferred in the profibus
side, even in case the slave does not contain these specific data
items.
The response time is highly dependent on the number of the
connected SPA slaves and the size of the configuration. For more
information, refer to Section 8.4.1. Gateway diagnostics.
When verifying signals in a multislave system, all the relays must be connected.
Otherwise the In Use flags of an entire slave might be deactivated.

Downloading configurations

When a configuration is defined, it is time to download it to the gateway by
following the instructions below:
1. If you have downloaded the configuration file directly after the configuration
definition described in the preceding Section 4.2. New configuration, jump to
step 2. In other cases, start the PCT and open the selected standard configuration
template by selecting File > Open in the main menu, and by double-clicking on
the wanted standard configuration template name.