Table 7.2.-3
Electromagnetic compatibility tests (Continued)
Radio frequency interference
test
Fast transient disturbance test
IEC 60255-22-4 and
IEC 60255-22-5
Surge immunity test
IEC 61000-4-5
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8
Voltage dips and
short interruptions
IEC 61000-4-11
Electromagnetic emission tests
EN 55011 and
IEC 60255-25
CE approval
Table 7.2.-4
Dimensions and weight
Type
SPA-ZC 302
conducted, common mode
IEC 61000-4-6 and IEC
60255-22-6
radiated, amplitude-
modulated
IEC 61000-4-3 and IEC
60255-22-3
radiated, pulse-modulated
ENV 50204
power supply
power supply
300 A/m continuous
30%, 10 ms
60%, 100 ms
60%, 1000 ms
>90%, 5000 ms
conducted RF emission
(mains terminal)
radiated RF emission
Complies with the EMC directive 89/336/EEC and the LV
directive 73/23/EEC
Dimensions [mm]
197 x 104 x 50
1MRS755014
10 V (rms),
f = 150 kHz...80 MHz
10 V/m (rms),
f = 80...1000 MHz
10 V/m, f = 900 MHz
4 kV
4 kV, line to earth
2 kV, line to line
EN 55011, class A
IEC 60255-25
EN 55011, class A
IEC 60255-25
Weight [g]
530