Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
Slave Menu includes the following commands:
Add
Add a slave
Remove
Remove a slave
Set address
Set address to the added slave
Prioritize
Prioritize a certain slave, can be either on or off
Import
Import the configuration to a certain slave

View

In the View drop-down menu, you can select whether to show or hide the toolbar
and the status bar in the window.
Fig. 5.4.5.-1
View menu

Refresh

To refresh the information in the Template info field, select View\Refresh in the file
menu, see Fig. 5.4.5.-1. The configuration file that is currently open in the Template
info window is reloaded from the disk.

Help

In the Help menu you will find the About function that shows general information
about the PCT.

Configuration options

SPA configuration

The SPA Configuration field is found on the left hand in the main window, see Fig.
5.3.-1, number 4. Here you can select and define several options when you load an
already saved configuration file, see the definitions below:
SPA Baudrate
In this drop-down box, you can select the baudrate to be used by
the gateway when communicating with the protection relay. The
default value is 9600 bauds.
SPA Reply
In this text field, you can define the value that will be used by the
Timeout
SPA gateway as a timeout value. Valid timeout values are 10 ms
to 500 ms. Default value is 50 ms.
SPA Idle Time In this text field, you can define the Idle time. Idle time is the time
that the gateway will wait before sending the next SPA message
when receiving the response of the previous sent SPA message.
Valid Idle time values are 5 -10 ms. The default value is 5 ms.
1MRS755014