Digital input, packed data type

If the datatype is P (= Packed), the SPA message format FirstCh/LastCh and
FirstDno/LastDno is used. The datatype numbering of Ch and Dno has to be
consecutive when the data type is packed.
The packed data type allows the gateway to read multiple binary data by using one
SPA command:
• Enabling faster updating of data, which is always polled and not updated by
events.
• Consuming less bytes on the profibus side.
This data is packed in 2 bytes in the profibus side. The first data is in bit number 0
and the second in bit number 1 and so forth.

Analog output

When you have opened a template with an analog output into the main window, you
can configure its settings that are shown in the Template info field as follows:
1. Select the signal you want to configure and click Edit, or double-click on the
signal.
2. A dialog is opened where you can modify the settings of that specific signal, see
Fig. 5.4.8.4.-1. The fields that you cannot configure are dimmed.
3. To save the new settings, click OK. To cancel, click Cancel to discard all
changes.
Fig. 5.4.8.4.-1 Analog Output configuration dialog
The definitions of the analog output signal settings are the following:
Description
Signal name
Slave Address
The slave address of the protection relay or unit
Ch/Cat/Dno
The Channel (Ch), Category (Cat), and the Data number (Dno)
where the specific Analog values are written to the SPA slave
device.
Scaling
Scaling factor, for details see Section 5.4.8.7. Scaling of
messages.
1MRS755014
A050368