Output - Siemens SITOP 6EP1336-3BA00 Manual

Power supply, modular 1ph/2ph
Table of Contents

Advertisement

6.2

Output

Output
Rated voltage U
DC
out rated
Total tolerance, static ±
Static line regulation, approx.
Static load regulation, approx.
Residual ripple in the load
range Peak-peak, max.
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
Adjustment range
Output voltage can be adjusted Yes
Output voltage setting
Remark
Output derating U
/T
out
Output derating U
/I
out
out
Output derating U
/U
out
i
Remark
Response when switching
on/off
Starting delay, max.
Voltage rise, typ.
Rise time of the output voltage,
max.
Rated current I
out rated
Current range
Remark
Active power output, typ.
Constant overload current for a
short circuit when powering up,
typ.
SITOP modular 1ph/2ph
Manual, 04.2018, C98130-A7548-A1-4-7629
6EP1333-3BA10
6EP1334-3BA10
(24 V/5 A)
(24 V/10 A)
Regulated, isolated DC voltage
24 V
3 %
3 %
0.1 %
0.1 %
0.1 %
0.1 %
50 mV
50 mV
200 mV
200 mV
24 - 28.8 V
Via potentiometer
Max. 120 W
Max. 240 W
See Figure 6-7 Output derating depending on the ambient temperature at Iout rated
(Page 42)
See Figure 6-8 Output derating depending on the output current at 60° C (Page 42)
-
-
U
overshoots by approximately 3 %
out
1 s
1 s
50 ms
50 ms
500 ms
500 ms
5 A
10 A
0 - 5 A
0 - 10 A
60 - 70 °C derating:
approx.
2 % I
120 W
240 W
6 A
12 A
6EP1336-3BA00
(24 V/20 A)
3 %
0.1 %
0.1 %
100 mV
200 mV
Max. 480 W
-
0.1 s
50 ms
500 ms
20 A
0 - 20 A
60 - 70 °C derating:
approx.
/K
2 % I
out rated
out rated
480 W
23 A
Technical data
6.2 Output
6EP1337-3BA00
(24 V/40 A)
3 %
0.1 %
0.1 %
100 mV
200 mV
Max. 960 W
See Figure 6-9
Output derating
depending on the
input voltage
(Page 43)
For 85 to 93 V AC, it
is not permissible
that the output volt-
age is set higher
than 24 V.
0.1 s
50 ms
500 ms
40 A
0 - 40 A
60 - 70 °C derating:
approx.
/K
2 % I
/K
out rated
960 W
46 A
39