Ambient conditions
Ambient temperature
Transport and storage tem-
perature
Humidity class
Mechanical stressing during
operation
Damaging gases
Atmospheric pressure
SITOP modular 1ph/2ph
Manual, 04.2018, C98130-A7548-A1-4-7629
6EP1333-3BA10 (24 V/5 A)
6EP1334-3BA10 (24 V/10 A)
-25 ... 70 °C for natural convection (self
convection)
Tested according to:
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-78 humid heat, constant
•
EN 60068-2-14 temperature change
•
-40 ... 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-30 humid heat, cyclic
•
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
Tested according to:
EN 60068-2-6 vibration, test Fc:
•
3.5 mm deflection in the range 5 – 8.4 Hz
2 g acceleration in the range 58 – 150 Hz
EN 60068-2-27 shock, test Ea:
•
acceleration 150 m/s
, test duration 11 ms
2
Tested according to:
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
•
Operation:
1080 - 795 hPa (-1000 - 2000 m)
•
For operation at altitudes of 2000 - 6000 m above sea level:
•
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m (see Figure 4-5 Mounting
height derating (Page 24))
Overvoltage category:
•
II up to 2000 m (EN 60950-1)
I from 2000 m up to 6000 m (EN 60950-1)
Storage:
1080 - 660 hPa (-1000 - 3500 m)
•
6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
0 ... 70 °C for natural convection (self con-
vection)
8
55