Siemens SITOP 6EP1336-3BA00 Manual page 38

Power supply, modular 1ph/2ph
Table of Contents

Advertisement

Technical data
6.1 Input
Integrated input fuse
Protection in the line
feeder cable (IEC 898)
Figure 6-1
38
6EP1333-3BA10
6EP1334-3BA10
(24 V/5 A)
(24 V/10 A)
Fuse
Fuse
T 3.15 A
T 6.3 A
Recommended for 1-phase operation: Minia-
ture circuit breaker, characteristic C (B), 6 A
(10 A);
Required for 2-phase operation: 2-pole coupled
miniature circuit breaker, characteristic C (B),
6 A (10 A) or for 230 V, 3RV2011-1EA10 circuit
breaker, (setting 3.8 A) or 3RV2711-1ED10
circuit breaker or for 400/500 V, 3RV2011-
1DA10 circuit breaker, (setting 3 A) or
3RV2711-1DD10 circuit breaker – according to
UL489-listed DIVQ
Power-failure buffering
6EP1336-3BA00
6EP1337-3BA00
(24 V/20 A)
(24 V/40 A)
Fuse
Fuse
T 10 A
T 16 A
Recommended for 1-
Recommended for 1-
phase operation: Min-
phase operation: Min-
iature circuit breaker,
iature circuit breaker,
characteristic C, 10 A;
characteristic C, 20 A;
Required for 2-phase
Required for 2-phase
operation: 2-pole cou-
operation: 2-pole cou-
pled miniature circuit
pled miniature circuit
breaker, characteristic
breaker, characteristic
C, 10 A or for 120 V,
C, 20 A or for 120 V,
3RV2411-1JA10 cir-
3RV2421-4BA10 cir-
cuit breaker or for
cuit breaker or for
230 V, 3RV2411-
230 V, 3RV2411-
1FA10 circuit breaker
1JA10 circuit breaker
Manual, 04.2018, C98130-A7548-A1-4-7629